Single Burning Item (SBI) Test Apparatus
Thông số cơ bản
Tiêu chuẩn: | EN 13823 |
Ứng dụng: | The single flame flammability tester is one of the primary tests for fire testing of building products and for evaluating product performance in angular configurations. |
Công nghệ phân tích: | Single flame flammability test |
Nhà cung cấp: | CONCEPT EQUIMENTSSBI |
Model: | SBI |
Công Ty TNHH Beta Technology chịu trách nhiệm phân phối chính hãng, mọi thắc mắc xin liên hệ số điện thoại 0903.042.747 hoặc email sales@betatechco.com để được hỗ trợ!
EN13823
The Single Burning Item (SBI) test is one of the series of the main Euroclass reaction to fire tests for building products and evaluates the performance of a product in a corner configuration. The apparatus is designed to comply with the international standard EN13823 and is relevant to classes A2, B, C or D (excluding floorings).
Specification & Features
- System comprises movable specimen holder, frame, hood, collector and measuring tube
- Left and right oriented specimen holders available
- Flow measurement utilising bi-directional probe and differential pressure transducer
- Temperature measurement at different locations inside the measuring tube
- Smoke measurement system according to DIN 50055
- Gas sampling probe
- 19” rack controller for main and auxiliary burners
- Gas flows measured by high accuracy Mass Flow Controllers
- Burners are fitted with flash-back protection and electronic flame sensors for enhanced safety
- Complete operating instructions
Options:
Gas analysis:
- Heated filter for connection to gas sample probe
- Heated sampling line
- Preparation of sample
- Oxygen, carbon monoxide and carbon dioxide analysers mounted in a 19” rack
Data acquisition:
- Includes 20 channel scanner
- IEEE interface card
- Software for a Windows environment(3.1, ’95, ’98, NT) which includes the possibility for automatic report generation
Personal computer:
- High end PC with 15″ screen
- Inkjet colour printer
19″ Computer rack:
- To house the PC, printer and data acquisition system
Technical Data & Requirements
Electrical Supply: 230V AC – 25A 50Hz
Burner Gas Supply: Commercial propane at 3bar(A) with a minimum purity of 95%.
Calibration Gas Supplies: Calibration and reference gases N2 and CO/CO2 to be available; we recommend:
- CO (0,4 Vol%) 1 to 2 bar (a)
- CO2 (3,5Vol%) 1 to 2 bar (a)
- N2 – 1 to 2 bar (a)
Requirements:
- A free height of minimum 4.5 metres in order to install the apparatus
- Room dimensions 3±0.2m x 3±0.2m x 2.4±0.1m (L x W x H) with a floor area of 9±2m²
- Flat floor for good positioning of specimen holder and for ease of use
- Power supply: 230V AC – 25A 50Hz
- Commercial propane at 3bar(A) with a minimum purity of 95%
- An extraction system should be capable of extracting 1m³/s; Under test conditions, the exhaust system should be capable of continuously extracting a volume flow, normalised at 298 K, of 0,50 m3/s to 0,65 m3/s